A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested while operating on emergency power.
|
11/22/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
x
|
|
Elevators that are equipped to operate on emergency power shall have signal/jewel at main landing to indicate emergency power operation.
|
11/22/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone shall work and give proper location/unit information.
|
11/22/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Communication loss monitor shall work.
|
11/22/2024
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
x
|
|
Bottom floor hoistway access limits shall work and stop motion at correct height.
|
11/22/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Both fire status panels shall work and be tested for fire service, EP, lock outs, etc.
|
11/22/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Need to test fire service phase 1 & 2, and door pressure.
|
11/22/2024
|