Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Both fire status panels shall work and be tested for fire service, EP, lock outs, etc. 11/22/2024
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches x Bottom floor hoistway access limits shall work and stop motion at correct height. 11/22/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Communication loss monitor shall work. 11/22/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested while operating on emergency power. 11/22/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) x Elevators that are equipped to operate on emergency power shall have signal/jewel at main landing to indicate emergency power operation. 11/22/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Need to test fire service phase 1 & 2, and door pressure. 11/22/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone shall work and give proper location/unit information. 11/22/2024