MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
There is no signage for Firefighters Operation by the phase I and phase II key switches. Obtain the correct signage from the building code addition that this elevator was designed to conform to.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The signage for “In Case of Fire” the missing. Install signage that conforms to the building code this elevator was installed to conform to.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
The hoistway door tension on P1, 2nd, 3rd, 4th, 10th, 11th, 12th, 13, and15th floor landings shall be adjusted to self-close.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - In phase II operation, the car doors are required to open with constant pressure on the door open button. The car doors currently open automatically. Reinspection required.
|
6/18/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide testing of the elevator on emergency power.
|
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide testing of the elevator emergency power selector switch.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
x
|
|
Provide testing of Phase II operations, record results.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
x
|
|
Provide testing of Phase I operations, record results.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
x
|
|
Provide MCP
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Provide guards on car bulbs to prevent accidental contact or breakage.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Provide existing emergency lights to have two working bulbs.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post Phase II operations in car.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
x
|
|
Numerous hoistway doors are not self closing, make so. Observed two broken door closer springs.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
A number of guide rollers have degraded to the point of replacement is required on the elevator car and counterweight. Replace the degraded rollers.
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)6
|
|
|
9th floor door closer arm needs to work.
|
5/20/2020
|