MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
Written evacuation procedures not on site for emergency personnel.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
Written evacuation procedures not on site
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Elevator machine room shall not be used for storage of non elevator equipment
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Elevator machine room shall not be used for storage of non elevator equipment
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Rupture valve is not sealed. A category 5 test shall be performed and the rupture valve shall be sealed in 2021.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Remove all non-elevator related materials from the elevator machine room.
|
|