Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.32 - Control Valve 303 x Check valve failed. Reg tagged elevator. 8/7/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be displayed in the machine room 7/12/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell shall work. 8/7/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light shall work. 10/21/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Over speed valve is not sealed and must have a category 5 weight test done within 90 days or less 7/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Unit has oil recovery pump. Replace pump with proper receptacle to collect oil leakage. 7/12/2023