Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Step indexing & comb plate impact devices need testing. Re-inspection required 3/24/2023
A17.1-1996 : Escalators 7.5 - Lighting 805.7 Lower demarcation light is out 12/7/2022
A17.1-1996 : Escalators 7.5 - Lighting 1009.2d Demarcation lights not working on both top and bottom. 12/21/2020
A17.1-1996 : Escalators 7.3 - Handrails 802.4 Left handrail needs to be replaced. 12/21/2020
A17.1-1996 : Escalators 7.10 - Operating and safety devices 805.3a Stop switch buzzer on top not working. 12/21/2020
A17.1-1996 : Escalators 7.5 - Lighting 805.7 Demarcation light not working at bottom egress 11/25/2019
A17.1-1996 : Escalators 7.5 - Lighting 806.2 Upper and lower demarcation lights are not working. Repair 10/7/2019
A17.1-1996 : Escalators 8.12 - Steps, step chains, and trusses 801.1 Step chain clearances do not meet requirement. RED TAGGED 10/7/2019
A17.1-1996 : Escalators 8.12 - Steps, step chains, and trusses 802.11 Entire truss needs to be cleaned out. 10/7/2019
A17.1-1996 : Escalators 8.2 - Stop switch 805.3e Upper level stop switch buzzer is not working. 10/7/2019
conversion conversion n/a Repair Demarcation lights 10/7/2019
conversion conversion conversion - reinspect x Complete Annual Test-step indecing-within 30 days 7/30/2018
A17.1-2016 : Elevators 7.3 - Handrails 8.6.8.1 Left handrail has a crack in it creating a pinching hazard. Replace handrail