Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone board has a loose connection, it will sometimes work, checked all the wiring and couldn't get the phone to work, repair or replace phone board in car operating panel 9/28/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The door is restrictor is missing parts, repair door restrictor so it works 8/13/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Perform monthly fire service test and post test log in the machine room 12/30/2019
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log has not been filled out since February 9/10/2020
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 The next 5 year test on the overspeed valve will be due in 2022 8/11/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x the 5 year test on the overspeed valve is due in 2022 9/28/2022