Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.14.2 Hydraulic Cylinders and Pressure Piping x x When conducting the 15 minute standing test, the elevator dropped down to the buffers, meaning there is a leakage in the hydraulic system somewhere 2/3/2022
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 1/20/2020
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 1/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired/replaced. Remove the recovery unit after the packing gland has been repaired/replaced and record the oil loss per A17.1 2016 - 8.6.5.5.7
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV is not sealed and must have a cat 5 weight test performed on or before the next inspection