Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/17/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Install Phase 1 Fire Service Instructions at 1st floor level 7/17/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 7/17/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 7/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 7/16/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No There is water leaking into the machine room and onto the controller. Correct source of leak and verify there is no damage to controller. Unit left turned off by maintenance company. 11/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency communications not working. Take corrective action and re-test. 5/11/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The emergency phone shall be operational when 110v source is disconnected. - Only working elevator in building - 14 days to correct violation. 8/6/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The emergency bell shall be operational when 110v source is disconnected. - Only working elevator in building - 14 days to correct violation. 8/6/2020
MO Minimum : Elevators (F) - Electrical Switches (F)6 Yes No Remove tape from slowdown & directional switches top of the hoistway and adjust 7/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Repair emergency light in car 7/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair emergency phone in car and secure phone line hanging in the machine room 7/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be operational. 11/12/2024