Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Alarm Bell - Replace Battery 12/6/2018
conversion conversion n/a Emergency Light - Replace Battery 12/6/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Upper hoistway access switch is missing halo ring, replace.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide a data plate indicating the A17.1 Code Edition to be used for inspecting the elevator
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Only fire service tested, passed. Hoistway was ran. ALL OTHER CAT 5 tests were not done. 8/3/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Need to repair alarm bell which is not working correctly. Re-inspection required 5/10/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Door restrictor is out of adjustment, repair as needed. 8/3/2023