A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and related on-site documentation shall be provided in the machine room. Fire service testing must be documented monthly. All documentation blank.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the equipment room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing/damaged pickup rollers (6F, 4F, 2F)
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete, need to test pull out, pull through, governor spin test, 125% brake test, car & counterweight buffer test, set safeties, unintended motion up & down and fire service test. Re-inspection required
|
1/3/2023
|