Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency phone shall work. 1/7/2020
A17.1-1996 : Elevators 3.8 - Top emergency exit 204.1e x The emergency exit switch shall be operational. The actuator is missing. The fact that it's missing should prevent the car from running, but is not. This was also reported in 2021. This shall be corrected and re-inspected within 14 days.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x The door restrictor shall work. 1/7/2020
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary power lowering operation shall be functional. (2nd Notice) 2/14/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The auxiliary power lowering operation shall be functional. 12/21/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 2/14/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The oil cooler shall not be powered from the cab lighting circuit. 3/26/2020
A17.1-1996 : Elevators 2.30 - Hydraulic Power Unit 1004.2(b)(13) The oil cooler shall be thermostatically controlled because the elevator has a viscosity cycle. 3/26/2020
A17.1-1996 : Elevators 3.8 - Top emergency exit 1001.2(c)(12) The emergency exit switch shall be operational. 2/14/2023
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 Label the disconnects with the feeder panel name, location and breaker numbers. 3/26/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) An ABC type fire extinguisher is required in the machine room. 3/26/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 2/14/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 2/14/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 2/14/2023