conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Door operator belt is worn out. Replace.
|
11/13/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
suspension ropes are below minimum diameter. Replace.
|
11/13/2018
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
x
|
2 of 4 hoist cables are rouged and stretched to maximum. Replace cables. Noted on 2017 report. Unit red tagged.
|
11/25/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Door restrictor not working.
|
11/25/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
|
|
Emergency light and bell not working.
|
11/25/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Program hands-free phone.
|
5/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Car door restrictor does not work.
|
12/15/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
When phase 1 recall was initiated, elevator 2 remained on the 8th floor. Phase 1 fire service is not working correctly
|
2/14/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Restrictor shall restrict the door from opening when not in a door zone. Repair restrictor
|
2/14/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean of all debris
|
9/21/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light does not work and must be repaired and be 5 foot candle minimum
|
9/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Each unit shall have a written MCP that is maintained on site
|
9/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Written maintenance control program shall be kept on site for each elevator.
|
9/21/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Clean trash out of pit.
|
9/21/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate in machine room.
|
9/21/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light does not work and must be repaired and be 5 foot candle minimum
|
7/5/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned of debris
|
7/5/2023
|