Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) x 2 of 4 hoist cables are rouged and stretched to maximum. Replace cables. Noted on 2017 report. Unit red tagged. 11/25/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work. 12/15/2021
MO Minimum : Elevators (I) - Pits (I)5 Clean trash out of pit. 9/21/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room. 9/21/2022
conversion conversion conversion - reinspect x Door operator belt is worn out. Replace. 11/13/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Door restrictor not working. 11/25/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Each unit shall have a written MCP that is maintained on site 9/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Emergency light and bell not working. 11/25/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work and must be repaired and be 5 foot candle minimum 7/5/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work and must be repaired and be 5 foot candle minimum 9/21/2022
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned of debris 7/5/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean of all debris 9/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Program hands-free phone. 5/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Restrictor shall restrict the door from opening when not in a door zone. Repair restrictor 2/14/2022
conversion conversion conversion - reinspect x suspension ropes are below minimum diameter. Replace. 11/13/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x x When phase 1 recall was initiated, elevator 2 remained on the 8th floor. Phase 1 fire service is not working correctly 2/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Written maintenance control program shall be kept on site for each elevator. 9/21/2022