Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone Autodial needs to be programmed to connect to number that is answered 24 hours a day seven days a week
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone did not work, phone line is dead, provide working phone line 10/1/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No Need new maintenance logs for 2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes No on fire service phase 1 recall after arriving at the recall floor the elevator doors automatically close after 60 seconds, the doors are to remain open 12/13/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No Replace burnt out ceiling lights in the elevator car 6/25/2026