A17.1-1996 : Elevators
|
2.4 - Machine space
|
1001.2(b)(4)
|
|
|
Auxiliary power lowering unit batteries are dead, replace batteries - Item 2.44 Rule 306.11
|
|
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(5) Oil Leakage Collection
|
|
|
Oil on pit floor, jack head was not draining into the pit bucket, clean up oil on pit floor
|
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light went out when the alarm bell is pressed, repair emergency lights
|
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
|
on fire service phase 1 recall after arriving at the recall floor the doors automatically close after 60 seconds, they are to remain open
|
12/13/2019
|