Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x on fire service phase 1 recall after arriving at the recall floor the doors automatically close after 60 seconds, the doors are to remain open 12/13/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x the batteries for the battery lowering emergency power are not holding a charge and need to be replaced 12/28/2022