Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No Need new maintenance logs for 2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes No on fire service phase 1 recall after arriving at the recall floor the doors automatically close after 60 seconds, the doors are to remain open 12/13/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No the batteries for the battery lowering emergency power are not holding a charge and need to be replaced 12/28/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a Yes No Pit has stagnant water in bottom and no pump to remove excess water
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone Autodial needs to be programmed to connect to number that is answered 24 hours a day seven days a week