A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone Autodial needs to be programmed to connect to number that is answered 24 hours a day seven days a week
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
No
|
No
|
Need new maintenance logs for 2026
|
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
Yes
|
No
|
on fire service phase 1 recall after arriving at the recall floor the doors automatically close after 60 seconds, the doors are to remain open
|
12/13/2019
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
Yes
|
No
|
Pit has stagnant water in bottom and no pump to remove excess water
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
the batteries for the battery lowering emergency power are not holding a charge and need to be replaced
|
12/28/2022
|