Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x on fire service phase 1 recall, after the elevator arrives at the recall floor the doors automatically close after 60 seconds. the doors are to remain open 12/13/2019
A17.1-1996 : Elevators 3.2 - Car top light and outlet 1001.2(c)(2) replace car top light bulb, it is burnt out 8/1/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 replace burnt out cab ceiling light bulb, required to have two working light bulbs 8/1/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x replace the emergency light battery, it is dead 8/13/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The state operating certificate on display in the machine room expired in 2020, a new copy is to be displayed annually 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts replace batteries in the battery lowering unit they are dead (Item 2.44 Section 3.26.10)