A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
1001.2(c)(2)
|
|
|
replace car top light bulb, it is burnt out
|
8/1/2022
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The state operating certificate on display in the machine room expired in 2020, a new copy is to be displayed annually
|
8/1/2022
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
replace burnt out cab ceiling light bulb, required to have two working light bulbs
|
8/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
replace batteries in the battery lowering unit they are dead (Item 2.44 Section 3.26.10)
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
replace the emergency light battery, it is dead
|
8/13/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
|
on fire service phase 1 recall, after the elevator arrives at the recall floor the doors automatically close after 60 seconds. the doors are to remain open
|
12/13/2019
|