A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
6/14/2023
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
100.3d
|
|
|
Remove non-electrical material from machine space.
|
9/19/2019
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV not sealed or tagged, notified on last visit, needs to be sealed & tagged within 90 days
|
8/23/2022
|
A17.1-2016 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(b)(2) Hydraulic elevator, dumbwaiter, or material lift Placed out of Service
|
x
|
x
|
Elevator leaked down 2" in 15 minutes. Placed out of service until repairs can be made.
|
8/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
MCP records should be kept on site for each elevator
|
5/27/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Phase II keyswitch is in-operable
|
8/23/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove debris in pit
|
5/27/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light in-operable
|
5/27/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Debris in pit
|
8/4/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light inoperable
|
8/4/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Reinspection of elevator phone. Still not working. repair phone.
|
7/13/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Reinspection of debris in elelvator pit. Still dirty. Clean elelvator pit.
|
8/15/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Reinspection of elelvator pit lights. STill not working. Repair pit lights.
|
8/15/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Re-inspection of elevator phone, still not working, needs repaired. Re-inspection required
|
7/31/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
x
|
|
Re-inspection of elevator pit lights, still not working. Need to repair lights. Re-inspection required
|
7/31/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Re-inspection of elevator phone, still not working. Needs repaired. Re-inspection required
|
8/15/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
x
|
|
Debris in pit.
|
9/8/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
x
|
|
Pit light inoperable.
|
9/8/2023
|