Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.4 - Machine space 100.3d No No Remove non-electrical material from machine space. 9/19/2019
MO Minimum : Elevators (I) - Pits (I)1 No No Remove debris in pit 5/27/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light in-operable 5/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No MCP records should be kept on site for each elevator 5/27/2022
MO Minimum : Elevators (I) - Pits (I)1 No No Debris in pit 8/4/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light inoperable 8/4/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Reinspection of debris in elelvator pit. Still dirty. Clean elelvator pit. 8/15/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Reinspection of elelvator pit lights. STill not working. Repair pit lights. 8/15/2023
A17.1-1996 : Elevators 2.32 - Control Valve 303 No No During The 15 Minute Holding procedure, the Elevator Technician determined oil leaking back into the tank. Repair or replace as needed. 11/18/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Re-inspection of elevator phone, still not working, needs repaired. Re-inspection required 7/31/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Yes No Re-inspection of elevator pit lights, still not working. Need to repair lights. Re-inspection required 7/31/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Re-inspection of elevator phone, still not working. Needs repaired. Re-inspection required 8/15/2023
MO Minimum : Elevators (I) - Pits (I)1 Yes No Debris in pit. 9/8/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Yes No Pit light inoperable. 9/8/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Reinspection of elevator phone. Still not working. repair phone. 7/13/2023
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Phase II keyswitch is in-operable 8/23/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 6/14/2023
A17.1-2016 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(b)(2) Hydraulic elevator, dumbwaiter, or material lift Placed out of Service Yes Yes Elevator leaked down 2" in 15 minutes. Placed out of service until repairs can be made. 8/23/2022
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV not sealed or tagged, notified on last visit, needs to be sealed & tagged within 90 days 8/23/2022