Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 2/17/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 6/4/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. (Currently no dial tone) 7/29/2021
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Replace the missing top floor pick up rollers. 1/9/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean. Remove excess debris. 11/8/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit lighting shall be operational. 1/9/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. Clean the pit. 1/9/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall work. Take corrective action as needed. 12/11/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 1/9/2023
conversion conversion conversion - reinspect x Phone volume is way too low in cab. Repair. 2/6/2019