Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/4/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Tested elevator on simulated emergency power. There are some problems in the transfer switch. Proper emergency power operation shall be tested once corrections are made. 5/4/2022
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1001.2(e)(2) x The counterweight runby is too short. Provide code compliant counterweight runby. 5/4/2023