Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 Replace the missing interlock cover at the 1st floor. 6/5/2020
MO Minimum : Elevators (A) - Hoistways (A)16 Replace the missing interlock cover at the 1st floor. 6/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Car position indicator shall be operational. 6/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Car position indicator shall be operational. 6/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency telephone shall be operational. 5/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents. 10/13/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The car position indicator shall be operational. 10/13/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Hoistway is in need of a clean down. 2/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x Phone does not work and the bell is not audible outside of the hoistway. Elevator Red tagged 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car does not work. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate Install a code data plate. It shall read "Missouri Minimum".
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams x The breaker box located in the machine room has exposed wires. Replace panel cover. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.2 Replacement of Suspension Means (Re-Inspection) x x The suspension ropes are undersized and rouging, ropes shall be replaced. Elevator Red Tagged. 6/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone is still not working. Alarm bell is now operational.
MO Minimum : Elevators (H) - Machine Rooms (H)8 x The breaker box located in the machine room has exposed wires. Replace panel cover.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit of dirt, debris, and trash.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than five (5) foot-candles at the pit floor.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit. 2/22/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) Governor rope date tag is missing.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site.
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys x x Could not test Phase I. Key switch on first floor is broken. 6/1/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Provide Phase 1 & 2 fire fighters instructions. 10/13/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Provide Phase 1 & 2 fire fighters instructions. 6/5/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Provide Phase 1 & 2 fire fighters instructions. 6/5/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 10/13/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.