Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Auxiliary battery lowering shall be operational. 11/4/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Battery lowering shall work. Take corrective action and retest. 11/6/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Battery lowering does not work. 7/1/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No 3.26.10 - Auxiliary power lowering shall be tested. 9/30/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service shall be tested. 9/30/2022
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Remove excess debris. 9/1/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be kept clean. Clean the pit. 7/3/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A monthly record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 7/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Car top light does not work. 7/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No The car top needs to be cleaned. 9/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Car top shall be kept clean. 7/3/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 7/14/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No The over-speed valve shall be tested with rated load. Note: This unit was originally scheduled for a category 5 test of the over-speed valve on this date. The hydraulic jack seal failed after the relief test on the other unit is this group of 2 cars. The building personnel didn't want any further testing on this group of two elevators. A re-inspection will need to be scheduled to complete the annual and category 5 test. 9/30/2022