MO Minimum : Elevators
|
(A) - Hoistways
|
(A)12
|
|
|
The hoistway wall was removed at the bottom landing behind the hoistway door during renovations. The wall needs to be replaced to maintain the fire rating of the hoistway
|
11/17/2025
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)12
|
x
|
|
The hoistway wall was removed at the bottom landing behind the hoistway door during renovations. The wall needs to be replaced to maintain the fire rating of the hoistway
|
12/8/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Provide Hall Station Pictogragh instructing occupants to "Use stairs in case of Fire"
|
3/7/2023
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered.
|
11/17/2025
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
No equipment unrelated to the operation of the elevator shall be added to elevator machine rooms. Newly installed pipes and plumbing need to be encapsulated in the wall.
|