Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits A 17.1 1996 1001.2(e) Water and oil shall not be allowed to accumulate on pit floors. PACKINGS LEAKING, SOAK PADS IN PIT (JACK PACKINGS NEED TO BE CHANGED, LOSING LOTS OF OIL) 8/20/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x A17.6-1996 ITEM 1.6 CAR EMG SIGNAL; 211.1(a)(3)phone battery backup not functioning. re-inspection required in 14 days 7/31/2023
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x A17.1 2016 - 8.6.5.16.5 OVERSPEED VALVE NOT SEALED, PERFORM REQUIRED 5 YR OSV TESTING WITHIN 90 DAYS, (Oct 8, 2021) PER MISSOURI DEPARTMENT OF FIRE SAFETY/ ELEVATOR SAFETY DIVISION 8/9/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone failed to operate recording call can not be completed as dialed. 11/14/2022