A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
A 17.1 1996 1001.2(e) Water and oil shall not be allowed to accumulate on pit floors. PACKINGS LEAKING, SOAK PADS IN PIT (JACK PACKINGS NEED TO BE CHANGED, LOSING LOTS OF OIL)
|
8/20/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone failed to operate recording call can not be completed as dialed.
|
11/14/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
A17.6-1996 ITEM 1.6 CAR EMG SIGNAL; 211.1(a)(3)phone battery backup not functioning. re-inspection required in 14 days
|
7/31/2023
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
A17.1 2016 - 8.6.5.16.5 OVERSPEED VALVE NOT SEALED, PERFORM REQUIRED 5 YR OSV TESTING WITHIN 90 DAYS, (Oct 8, 2021) PER MISSOURI DEPARTMENT OF FIRE SAFETY/ ELEVATOR SAFETY DIVISION
|
8/9/2022
|