MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency telephone shall be operational.
|
8/18/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/22/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
The stairs and handrail that lead to the machine room and rotting and in need of repair.
|
8/22/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
This inspection started in the morning, there was no working alarm, 2-way communication, or emergency light, and an issue with access to the hoistway. The elevator was red tagged.
|
10/14/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
After the elevator was red tagged in the morning, the maintenance company was able to correct the red tag items and the red tag was removed. The annual inspection and category 1 test still need to be completed. Only soft set of the safeties and spinning of the governor was completed.
|
10/25/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean.
|
11/17/2022
|