Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(a) Elevators Placed in Inactive Status x x This unit has been placed out of service and in inactive status according to CSR-40-5.090. The car has been properly positioned in the hoistway, all doors are in closed position, fuses removed and stored in a separate location, red tagged and locked out of service. The elevator can remain in this state for a maximum of 2 years.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 Car door optical reopening does not work and shall be repaired. 2/3/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a current MO State operating certificate in the machine room. 6/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Scavenger pumps are not permitted to be used as means to return oil to the tank. 6/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. 6/16/2022