MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
|
6/16/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a current MO State operating certificate in the machine room.
|
6/16/2022
|
conversion
|
conversion
|
n/a
|
|
|
Emergency bell is not operational.
|
2/3/2021
|
conversion
|
conversion
|
n/a
|
|
|
Emergency light does not operate.
|
2/3/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Scavenger pumps are not permitted to be used as means to return oil to the tank.
|
6/16/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
The presence of an overspeed valve has been confirmed. The overspeed valve shall be scheduled for the category 5 test required by A17.1 2016 8.6.5.16.5 on or before the next annual due date per MO AHJ.
|
2/22/2024
|