Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone line not working properly 10/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Yes Yes During the 15 minute static load test the car leaked down continuously with, and without both valves closed. The source of the leak shall be determined, and repaired. 8/8/2025
A17.1-2016 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 2.22.3.3 Yes No The car buffer information tags are not present and shall be installed. Allrise responsibility. 8/8/2025
A17.1-2016 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 2.22.3.3 Yes No The car buffer information tags are not present and shall be installed. Allrise responsibility. 8/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Yes No Hydraulic control valve is leaking fluid back into the hydraulic tank during the 15 minute standing test, car dropped 3 inches. Repair or replace control valve. Re-inspection required 1/27/2026