Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace worn guide rollers / shoes on the top of counterweight 11/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. 11/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Post Phase I instructions near the f/f switch in the lobby.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No Emergency light in the cab does not work on emergency 110v power 11/12/2023
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Provide current year tested fire extinguisher in the elevator machine room.
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Provide testing of the elevator on emergency power.
A17.1-1996 : Elevators 4.12 - Standby power selection switch 1002.2g Yes No Provide testing of the elevator emergency power selector switch, located in the Fire Command Room.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The fireman service phase I key switch housing is damaged and shall be replaced. Reinspection required. 7/29/2022
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) Yes No There is a top and bottom guide roller on the counterweight that has deteriorated and shall be replaced. 7/29/2022
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) No No The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 11/7/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes Yes One of the suspension ropes has frayed/broke. Ropes shall be replaced and reinspected 11/12/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Elevator pit shall be cleaned 11/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove non elevator related materials from machine room 11/7/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 8/21/2023