Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 11/7/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The fireman service phase I key switch housing is damaged and shall be replaced. Reinspection required. 7/29/2022
A17.1-1996 : Elevators 1.12 - Car enclosure 204 Handrail on back is loose and shall be corrected 11/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. 11/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The elevator car top is covered with an extreme amount of dust and shall be cleaned. 11/7/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 8/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Handrail on back is loose and shall be repaired 11/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove non elevator related materials from machine room 11/7/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned 11/7/2023