MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone does not work, needs repaired. Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Elevator cab emergency lights do not work, needs repaired. Re-inspection required
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Stop switch in pit needs to be re-fastened to the wall for proper operation,
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
Stop switch in pit needs to be refastened to wall for propoer operaton
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Place current state operating certificate in elelvator machine room. Rule 40-5.100(2)
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate.
|
6/22/2020
|
conversion
|
conversion
|
n/a
|
|
|
Replace or re groove drive sheave cable bottomed in groove
|
9/3/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work on batery backup
|
6/4/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The following testes need to be performed to complete Cat. 5 inspection: 125% brake, full load, full speed safeties, car and conterweight buffers.
|
6/4/2024
|