Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work, needs repaired. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Elevator cab emergency lights do not work, needs repaired. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 Stop switch in pit needs to be re-fastened to the wall for proper operation,
MO Minimum : Elevators (I) - Pits (I)7 Stop switch in pit needs to be refastened to wall for propoer operaton
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Place current state operating certificate in elelvator machine room. Rule 40-5.100(2)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. 6/22/2020
conversion conversion n/a Replace or re groove drive sheave cable bottomed in groove 9/3/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work on batery backup 6/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following testes need to be performed to complete Cat. 5 inspection: 125% brake, full load, full speed safeties, car and conterweight buffers. 6/4/2024