Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)3 Rear elevator car door re-opening device does not work. Electric eye repair door re-opening device
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work, needs repair or replaced. Re-inspection required 6/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Unable to test the emergency car lighting and signaling devices. The 110V disconnect for those systems could not be located. Locate and label the disconnect so the emergency systems can be tested properly. 6/23/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Elevator pit light does not work, new light bulb did not rectify problem. Problem may be in pit light wiring or light fixture.
MO Minimum : Elevators (I) - Pits (I)7 Elevator pit stop switch is loose and needs to be secured to wall in pit.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following tests still need to be performed to complete the cat 5 inspection: full load, full speed safeties and 125% brake 6/7/2023
conversion conversion conversion - reinspect x Phone is cab does not work 5/22/2019
conversion conversion conversion - reinspect x Cab Emergency lights do not work 5/22/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated Missouri Operating Certificate in machine room