Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.12 - Car enclosure 204 top floor both oull chain car top access boxes need to be repaired 6/15/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Need a maintenance control progem on site posted on controller by or on next inspection
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Peform monthly fire service testing and document on log in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace car gate astragal cover. Astracal not working
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Remove gauge from control valve. Replace with a test port
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Test overspeed valve on or before 4/25/22
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance discharge hose in tank split open needs to be replaced
conversion conversion n/a Repair pit light 6/15/2020