Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x The shut off valve in the pit is under-rated and shall be replaced. 10/31/2018
conversion conversion n/a It is recommended a full length door reopening device (light ray) be installed. 10/31/2018
conversion conversion n/a Open electrical box in machine room ceiling requires a cover. 10/31/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency light shall work. 8/4/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm bell shall work. 2/14/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/4/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational and code compliant. 10/14/2022