Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 the top seal of the jack packing is dry rotted and falling apart, replace the packing
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log does not have monthly fire service test log in the machine room 11/21/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 Remove shelf for video surveillance system in the machine room that is no longer being used as it restricts the work area for the controller. 11/21/2019
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2(A) Replace the check valve, the elevator settled into the pit during the set test. The elevator did not move when the machine room gate valve was turned off 11/21/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device x x the check valve needs o be replaced, car settled 4.5 inches in 15 minuets. didn't move at all when the gate valve was closed 6/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device x x Elevator still settled 4 inches in 15 minutes, with the machine room shutoff turned off the elevator doesn't move, valve is not holding the elevator, repair replace valve 7/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone did not work, provide working phone line, used test phone and the line is dead 11/4/2024