MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not work, provide working phone line, used test phone and the line is dead
|
11/4/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove shelf for video surveillance system in the machine room that is no longer being used as it restricts the work area for the controller.
|
11/21/2019
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(A)
|
|
|
Replace the check valve, the elevator settled into the pit during the set test. The elevator did not move when the machine room gate valve was turned off
|
11/21/2019
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
the top seal of the jack packing is dry rotted and falling apart, replace the packing
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
does not have monthly fire service test log in the machine room
|
11/21/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device
|
x
|
x
|
the check valve needs o be replaced, car settled 4.5 inches in 15 minuets. didn't move at all when the gate valve was closed
|
6/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device
|
x
|
x
|
Elevator still settled 4 inches in 15 minutes, with the machine room shutoff turned off the elevator doesn't move, valve is not holding the elevator, repair replace valve
|
7/28/2021
|