Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)9 Capacity Plate No No Provide capacity plate for car 9/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Provide working 2 way communication 9/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Provide emergency light and bell 9/7/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No Provide rope data tag 9/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 2.20.2 No No no rope data tage 11/18/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No runby less than 6 ins cant reach final limit need to shorten ropes 9/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) No No fire hat jewell missing 11/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Provide rope data tags. 11/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) Yes No Shorten ropes to allow unit to activate final 9/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No REMOVE TRASH AND DEBRIS FROM PIT 11/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No pit has standing water an trash 11/18/2024
conversion conversion conversion - reinspect Yes No Emg. phone not working 8/20/2019
conversion conversion conversion - reinspect Yes No runby less than 2 ins. need to shorten cables 8/20/2019
conversion conversion conversion - reinspect Yes No Car top oily an dirty an shall not be used for storage 8/20/2019
conversion conversion conversion - reinspect Yes No Water an oil shall not be allowed to accumulate on pit floor pit has a lot of trash in it. 8/20/2019
conversion conversion conversion - reinspect Yes No No data tags on Hoist ropes 8/20/2019
conversion conversion conversion - reinspect Yes No Car door restrictor not working. 8/20/2019
conversion conversion conversion - reinspect Yes No Missing fire hat covers in car an at hall sta. 8/20/2019
conversion conversion conversion - reinspect Yes No No gov. rope tags 8/20/2019