Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) the fire service test log has not been filled out for the last 3 months 3/2/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Provide “ABC” type fire extinguisher in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x fire service phase 1 recall did not work properly. When the elevator doors were open on a floor other than the recall floor and the phase 1 keyswitch was turned on the elevator would remain at the floor that it was on and not close the doors and return to the recall floor. When the elevator doors were closed the elevator would return to the recall floor. Unit was not Red Tagged since it is the only elevator in the building. 1/31/2023
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a copy of the state operating certificate is to be posted in the machine room 10/24/2022