Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Elevator not responding to phase I recall. 10/19/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 5/28/2020
MO Minimum : Elevators (A) - Hoistways (A)1 Landing door gibs badly worn, all floors. 1/27/2021
MO Minimum : Elevators (A) - Hoistways (A)1 Landing door missing pick up roller. FL 1 1/27/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 8/30/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide fire service testing log in machine room, and document monthly testing. 1/27/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP, or location of MCP in machine room. 1/27/2021