MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) x The oil loss log in the maintenance control program (MCP) indicates that a significant amount of oil loss has occurred. The annual required pressure test was performed with no significant loss detected. However, the elevator on the following day required oil to reach the top landing. Another pressure test was performed with no significant loss detected. A full load pressure test will be required to determine the oil loss of the system. 9/6/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Failed Cat 1 Firefighters service test. Door open button does not work on phase II. Red-tagged elevator, Re-inspection required
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Machine room shall have on site Maintenance records. 9/10/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back up power device (battery) has failed. The fixture shall be repaired to operate. Re-inspection required
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm inoperable on battery. Re-inspection required