Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Overhead lighting above pump and controller not working.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide an up to date fire extinguisher in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit, and provide a pit jug not to exceed 5 gallon capacity.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Provide a pit light and switch, and a GFCI outlet in pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x Redpair the emergency lights and bell.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase I does not overide the building security.
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase II fire service not working. 5/23/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm not working. 5/29/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)2 Cartop stabilizers out of adjustment causing lateral movement of car. 10/21/2021
MO Minimum : Elevators (I) - Pits (I)1 Debris in pit. Clean. 10/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency phone not working. 4/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP, or location of MCP in machine room. 4/27/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting inadequate. 4/27/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 Oily rags and old oil dry present on machine room floor. Clean. 4/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide type ABC fire extinguisher in machine room. 5/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit, and replace with a pit jug not to exceed 5 gallon capacity. 8/30/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Provide a pit light in pit with switch accessible from landing door. 8/30/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 8/30/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Overhead lighting above controller not working. 8/30/2022