Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)6 x Basement landing door interlock failed. Door is able to be opened when car is not there. 10/23/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone not working at time of inspection. 10/23/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency lighting not working. 10/21/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Door providing access to machine room not able to be opened from the inside without the use of a key. 10/21/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Only 1/2" of CW runby in pit. 10/23/2018