MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
7/2/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Properly secure the emergency exit as specified by the code.
|
7/2/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept dry. Remove fluids from the pit and provide means to prevent accumulation of ground water from entering the pit.
|
7/2/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting shall work.
|
7/2/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The covers are missing from the hoistway door interlocks on the 2nd and 3rd floors.
|
7/2/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
7/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace faded Phase 2 fire service signage.
|
8/19/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit light shall work.
|
8/19/2024
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Replace missing interlock covers (exposed live wiring).
|
8/19/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Attach the escape hatch to the car and secure it so that it is only openable from the outside without the use of tools.
|
7/2/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
There were no keys on-site to test fire service. Keys to activate fire service shall be kept on-site at all times and fire service shall be tested to complete the annual inspection.
|
7/22/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The emergency light and alarm shall be tested to complete the annual inspection.
|
7/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell doesn't work.
|
8/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service operation shall be tested. Keys were not on-site to test fire service.
|
8/13/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The alarm bell on the car top is weak and shall be repaired or replaced.
|
7/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency lighting shall work.
|
10/22/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency telephone shall work.
|
10/22/2020
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)5
|
x
|
x
|
The car safeties failed to operate the SOS switch. Unit Red Tagged.
|
11/10/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Governor pull out and pull thru and 125% brake test have been completed. The remaining items of the category 5 test and the annual inspection still need to be performed.
|
11/10/2020
|