Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)10 2. Access means shall be provided at one upper landing to permit access to the top of the car, and at the lowest landing if this landing is the normal point of access to the pit. This car has no means of cartop or pit access from the landings. 1/7/2020
MO Minimum : Elevators (A) - Hoistways (A)16 3. The cartop light must be guarded to prevent damage when accidentally hit by a person moving onto or around on the car top. No light guard. Item 3.2 1/7/2020
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 1. Bulbs or tubes shall be guarded to prevent breakage. Bulbs are not guarded. 1/7/2020
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 The cab celing is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 1/7/2020
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 The freight car enclosure shall have capacity plate, loading class plates, and a "No Passengers" sign conspicuously posted. Letters shall not be less than one-half inch (1/2") high. 1/7/2020
MO Minimum : Elevators (D) - Brakes (D)2 x x 7. For passenger elevators and all freight elevators, the brake shall be tested for compliance with applicable requirements. Place the load (125%) in the car and run it to the lowest landing by normal operating means. The driving machine shall safely lower, stop, and hold the car with this load. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.4 9/14/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. 6/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required 3/28/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. 1/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The elevator drive machine will not hoist a 100% capacity load in the up direction. The drive machine shall be repaired or replaced to hoist the rated capacity. The elevator was removed from service and a re-inspection is required before the elevator can be returned to service. 1/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 1/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing and locking and shall be openable from inside without use of key.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be made self closing/self locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door required to be self closing self locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be made self closing / self locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 MACHINE ROOM DOOR SHALL BE MADE SELF CLOSING / SELF LOCKING.
MO Minimum : Elevators (I) - Pits (I)1 4. All pits shall be kept dry, clean and free of equipment or material not relating to the operation of the elevator. Water in pit sump pump not working and miscellaneous debris in pit. Needs to be cleaned out and sump pump fixed. 1/7/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x 8. Type B safeties shall stop the car with the rated load within the required range of stopping distances for which the governor is tripped. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.1(a) 9/14/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x 6. The governor rope pull-through and pull-out forces shall be tested to determine conformance with the applicable requirements, and the adjustment means shall be sealed. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.2(b) 9/14/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)7 x x 5. The tripping speed of the governor and the speed at which the governor overspeed switch, where provided, operates shall be tested to determine conformance with the applicable requirements and the adjustable means shall be sealed. Never checked for 5-year testing. This is a re-inspect. 8.11.2.3.2(a) 9/14/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room.